Lab #3
Experiment
#1
Air Flow Rig
Fluid Mechanics Lab
-
Abstract
-
The fluid flow rates and
pressure drops through various common piping constructs are all
subject to Bernoulli’s Equation – energy is conserved
(though viscosity and friction losses must be taken into account).
Changes in pressure result in a change in velocity when the energy
of the fluid is constant.
-
- Introduction
-
- Each of the
devices in the air flow rig can be used for velocity and/or flow
rate measurement in a pipe, and each one will impart its own level
of pressure drop (energy loss) on the fluid.
-
-
Figure 1: Air Flow Rig
- Velocity measurement
using the pitot tube is based upon the fact that when a flow strikes
the rounded tip of the tube, a stagnation point is created where
velocity is zero. According to Bernoulli’s Equation, all of
the velocity head is converted to pressure head – the pressure
at this point is the maximum. Holes along the side of the tube
measure the “ambient” pressure inside the pipe. The
difference between the two pressures represents the velocity head
which had been converted to pressure at the stagnation point.
(1) Pitot Tube Velocity
-
Equation 1 represents the
velocity in terms of pressure difference – it is derived from
Bernoulli’s Equation. The velocity profile for the pitot tube
should appear to be low near the wall of the pipe (due to viscous
forces slowing down the flow) and plateau as the tube is moved away
from the wall of the pipe (due to turbulent flow the velocity is
essentially constant except near the pipe walls).
(2) Volumetric Flow Rate
through Orifice
-
Equation 2 represents
flow through an orifice. Like a venturi, an orifice limits the
diameter of the pipe and converts pressure head into velocity head.
Also like a venturi, this does not happen in the real world without
loss. A flow coefficient (Cf) is used to correct for the
energy which is converted to heat due to viscous forces as the air
flows through the orifice.
-
Elbows causes pressure
drop due to the fact that the fluid must change direction. The
fluid’s inertia attempts to resist such changes and causes
pressure gradients in the elbow resulting in virtual flow
constriction and turbulence which again cause energy to be
dissipated. Equation 3 represents the derivation of the loss
coefficient for an elbow assuming that the other variables are
known. Equation 5 represents the flow rate through an elbow. A loss
coefficient, K, is once again used to account for the energy losses.
-
(3)
Minor Loss Coefficient,
used in determining head loss through fittings.
(4)
Rearrangement of Equation
3, determining velocity with a known constant, K.
(5)
Volumetric
Flow Rate through 90 degree elbow.
- Nozzles once again
act as flow constrictions, very similar to a venturi. The pressure
drop, difference in cross-sectional area, and a discharge
coefficient to correct for loss are used to determine flow rate with
a nozzle. The difference in cross-sectional areas of the inlet and
outlet (throat) determines the flow rate through the nozzle with a
given pressure drop. Equations 6 and 7 describe the mass flow rate
and volumetric flow rates through a nozzle, respectively.
-

(6) Mass flow rate through
nozzle
(7) Volumetric flow rate
through nozzle
-
- Procedure
-
Four distinct
differential pressures are measured – a pitot tube and
pressure drop across an orifice, 90° elbow, and nozzle. A
digital manometer is connected between the two measurement points of
each fitting, the fan is turned on and air pressure difference
measured. (The manometer reports the pressure on each point relative
to atmospheric pressure – “zero”).
- For the pitot tube,
six points at a constant flow rate on the radius of the pipe are
measured. (These points are represented by r in Table 1). The
velocity will be different at the periphery of the pipe due to
viscous forces slowing the flow.
- The orifice, elbow,
and nozzle pressure drops are all measured sequentially at five
different flow rates (A flow rate is set, the pressure drops of each
device are measured, then the flow rate is changed and the
measurements repeated, for a total of five times). This allows each
device to be used as a flow meter and the results to be compared.
- Results and
Discussion
-
- For all
results, the density of air is assumed to be 1.220 kg/m3.
All Δp values are pressure losses.
The major diameter/area of the pipe is 0.1524 m / 0.018 m2.
The orifices and nozzles will constrict this down to a level, given
above the respective data tables.
-
Table 1:
Pitot tube experimental data and results
|
Trial |
Δp
(Pa) |
r
(m)* |
V
(m/s) |
Q
(m3/s) |
|
1 |
14 |
0.0762 |
4.791 |
0.0874 |
|
2 |
7 |
0.0699 |
3.388 |
0.0618 |
|
3 |
7 |
0.0572 |
3.388 |
0.0618 |
|
4 |
7 |
0.0445 |
3.388 |
0.0618 |
|
5 |
7 |
0.0318 |
3.388 |
0.0618 |
|
6 |
7 |
0.0191 |
3.388 |
0.0618 |
- The radius r is the
distance that the pitot tube is inserted into the pipe, therefore
the larger number means that the tube is closer to the center.
Velocity is found from Equation 1 and volumetric flow rate by
multiplying this by the cross-sectional area of the pipe. The
results were fairly inconclusive as the pressure difference should
have been less on the periphery of the pipe and fairly constant in
all other regions. A peak was experienced when the pitot tube was
fully inserted, indicating a higher velocity in the center of the
pipe. Due to the turbulent flow (Re ≈
1.9 x 105), this should not have been so defined.

Figure 2: Velocity Profile
as measured by pitot tube – higher Radial Distance = closer to
center of pipe.
Table 2: Orifice
experimental data and results (Cf=0.8, A0=0.153
m)
|
Trial |
Δp
(Pa) |
Q
(m3/s) |
|
5 |
6 |
0.0385 |
|
4 |
7 |
0.0415 |
|
1 |
14 |
0.0587 |
|
2 |
34 |
0.0915 |
|
3 |
145 |
0.1891 |
- The orifice results
were more sensible, with increases in pressure loss representing a
marked increase in flow rate. Volumetric flow rate through an
orifice is calculated from Equation 2, derived from Bernoulli’s
Equation with the coefficient of flow taken into account. The
ordering of the trials is based upon the fan speed which was used
during that trial – from lowest to highest. This is the case
through the elbow and nozzle measurements as well, as the same speed
of fan was used for the respective measurements of those devices as
well.
-
Table 3:
Elbow experimental data and results (K=0.19)
|
Trial |
Δp
(Pa) |
V
(m/s) |
Q
(m3/s) |
|
1 |
0 |
0.0000 |
0.0000 |
|
2 |
0 |
0.0000 |
0.0000 |
|
3 |
0 |
0.0000 |
0.0000 |
|
4 |
7 |
1.4766 |
0.0269 |
|
5 |
7 |
1.4766 |
0.0269 |
- The velocity and
volumetric flow rates through the elbow were calculated using
Equations 4 and 5, respectively. The value K of 0.19 is obtained
from Crowe, page 337 Table 10.5, with a 90° smooth bend of
radius/diameter ratio of 2. An elbow with a tight radius will cause
greater pressure drop as fluid is forced to change direction but an
elbow with a large radius will incur pressure drop as well due to
the long length of pipe. According the Crowe Table 10.5, a r/d ratio
of 4 seems to be optimal. The elbow presented a bit of difficulty as
some of the trials produced a pressure loss of zero – it may
have been below the scale of the manometer or there may have been a
leak, but a pressure drop of seven pascals was obtained in the last
two trials. A pressure drop of zero technically means there is no
flow, but there WAS in fact flow it was not being measured properly.
The flow rate resulting from this compared with the orifice
measurement is quite a bit lower.
Table 4:
Nozzle experimental data and results (C=0.98, Athroat=0.00456
m2)
|
Trial |
Δp
(Pa) |
Qmass
(kg/s) |
Q
(m3/s) |
Percentage
of orifice Q value (%) |
|
4 |
21 |
0.0330 |
0.0271 |
65.20 |
|
5 |
28 |
0.0382 |
0.0313 |
81.32 |
|
1 |
28 |
0.0382 |
0.0313 |
53.23 |
|
2 |
61 |
0.0563 |
0.0462 |
50.42 |
|
3 |
249 |
0.1138 |
0.0933 |
49.33 |
- The results of the
nozzle were more in line with those obtained from the orifice, at
least compared with the elbow. The percentage of flowrate compared
with the flowrate obtained by the orifice method is listed in the
last column of Table 4. Nozzle mass flow rate was determined using
Equation 6. The fact that the pressure was not exactly atmospheric
the density of air is not exactly the 1.22 kg/m3 assumed,
but the pressure difference compared with atmospheric was so low
that the effect is negligible. The nozzle discharge coefficient was
assumed to be 0.98.
- Conclusions
-
Orifices and
nozzles can effectively be used to determine flow rate and/or
velocity through a closed pipe. Pitot tubes can determine velocity,
and if they are within a closed channel (e.g. a pipe), the flow rate
can be found, especially where flow is turbulent and velocity is
essentially constant throughout the cross-section of the pipe.
Elbows, while not an extremely effective flow determining device,
can incur significant pressure loss, especially if they are tightly
bent or have a very long radius.
- References
-
-
1. Crowe, Clayton T.,
Donald F. Elger, Barbara C. Williams, and John A. Roberson.
Engineering Fluid Mechanics. 9th edition. John Wiley &
Sons, 2009.
-
-
-